Background Image
Table of Contents Table of Contents
Previous Page  129 / 156 Next Page
Information
Show Menu
Previous Page 129 / 156 Next Page
Page Background

Electrical Theory & Applications for HVACR  

Chapter 6:  Troubleshooting 

Page 117 

winding.  Evaporator superheat, total superheat, and 

condenser sub‐cooling, along with sucƟon pressure and 

head pressure, must be taken for the system check.  In 

this case, the technician took a system check and found 

the evaporator superheat to be very high at 40° and 

the total superheat to be very high at 90°.  Condenser 

sub‐cooling was fine at 12°.  Both sucƟon and head 

pressure were low (see Figure 6‐14).  The problem that 

caused the overheaƟng was a faulty thermostaƟc 

expansion valve.  The valve would not open enough, and the enƟre low side of the system was being 

starved.  The compressor was a refrigerant‐cooled compressor.  This caused the compressor to 

overheat and cycle on its overload unƟl the run winding finally opened.  Without this final system 

check, the new compressor would surely fail in a short Ɵme. 

VOLTMETER OR OHMMETER?

OŌen service technicians will encounter switches in series or parallel with electrical loads.  Keeping 

the electrical power on and using a voltmeter to voltage troubleshoot is the fastest and most reliable 

method.  However, there will be Ɵmes when a technician must switch to an ohmmeter and shut the 

electrical power off in order to get to the root of the problem. 

Figure 6‐15 shows an electric PSC motor in series with two switches that are in parallel with one 

another.  The voltage between points A and B (the open switch), in this case, would be zero volts 

because the voltmeter would be measuring between Line 1 and Line 1.  The voltage between points C 

and D (the closed switch) would also be zero volts because of the voltmeter measuring between Line 

1 and Line 1 again.  Remember, the motor is running and dropping all of the 230 volts while it is 

consuming power.  A voltmeter across the R and S terminals of the PSC motor would read 230 volts 

because the meter is measuring the voltage between Line 1 and Line 2, which is 230 volts. 

Figure 6‐15 showed us that a voltmeter across the R and C terminals of the PSC motor would read 230 

volts because it is measuring between Line 1 and Line 2.  However, what would the voltage be 

between R and C if the run winding between R and C opened, causing the motor to stall and draw 

Fig. 6‐14 

Fig. 6‐15 

Fig. 6‐16