Background Image
Table of Contents Table of Contents
Previous Page  42 / 156 Next Page
Information
Show Menu
Previous Page 42 / 156 Next Page
Page Background

Page 30 

Chapter 2:  Circuits and Their Components 

Electrical Theory & Applications for HVACR  

open or close.  The electrical circuit to the relay coil is enƟrely 

separate from the circuit through the relay contact.  The coil 

voltage may be 24 volts and the circuit through the relay 

contacts may be 120 volts.  Thus, low voltage is used to control 

a switch that controls a high‐voltage load.  See Figure 2‐23. 

Relays oŌen contain more than one set of contacts or switches.  

Relay contacts are always shown as normally open (NO) or 

normally closed (NC) with the coil in the de‐energized posiƟon.  

Energizing the coil causes the contacts to change posiƟon. The 

relay contacts have low current raƟngs, with a maximum of 10 

amps being considered normal.  Current flow in the coil circuit 

is very low, oŌen less than 1/4 ampere.  A 24‐volt control 

circuit is safer for personnel, permits the use of smaller wire, and causes less arcing at the switch. 

A lock‐out relay is a relay with approximately 75 percent more resistance than the coil of the control 

it locks out.  This difference allows for the proper voltage drop so that one coil will energize and the 

other will not.  It is wired in a circuit as shown in Figure 2‐24. 

SEQUENCER

If mulƟple loads are energized at the same Ɵme, an overwhelming current surge or load is placed on 

the power supply.  When this occurs in a residenƟal home, lights may dim or flicker; in a commercial 

building, electrical demand for purchased electrical energy will be billed at a high‐demand rate for 

the enƟre month. 

Sequencers are Ɵme‐delay relays that stage loads on and off and are commonly found on electric 

heaƟng systems connected to heaƟng elements. 

CONTACTORS

A contactor is an electrical switching device that operates much like a relay.  However, the contactor 

has heavy‐duty contacts for controlling larger loads.  These contacts are normally open (NO) and 

controlled by a magneƟc coil.  When the coil is energized, the contacts close.  Contacts are used to 

open or close a circuit between the main power supply and the load and are rated according to the 

maximum amperage flow through the contacts for a specific voltage.  A two‐pole contactor has two 

separate contacts and is used to control 240‐volt single‐phase circuits (for residenƟal air 

Fig. 2‐23:  The coil circuit is separate 

from the motor circuit 

Fig. 2‐24:  Lock‐out relay circuit