Background Image
Table of Contents Table of Contents
Previous Page  40 / 156 Next Page
Information
Show Menu
Previous Page 40 / 156 Next Page
Page Background

Page 28 

Chapter 2:  Circuits and Their Components 

Electrical Theory & Applications for HVACR  

LOW-VOLTAGE TRANSFORMERS

Step‐down transformers have less windings in the secondary than the primary, which makes 

resistance less in the secondary.  A 240‐volt primary has a raƟo of 10:1 windings for a 24‐volt 

secondary; a 120‐ to 24‐volt has a raƟo of 5:1 for 24 volts. 

Twenty‐four‐volt control transformers used in HVAC equipment have a volt‐amp raƟng between 16 

and 50.  To find the amperage capacity of a low‐voltage transformer, divide the volt/amp (VA) raƟng 

by the secondary voltage output. 

Example: 

RaƟng: 24 volts/40 VA 

40 VA ÷ 24 volts =

1.7 amps maximum secondary load

Most transformers have an internal fuse to prevent the transformer from high‐amperage burn‐out.  

Some manufacturers install a ±2 amp Ɵme‐delayed fuse in the secondary side for addiƟonal 

protecƟon. 

Some equipment has two transformers: one in the indoor unit and one in the outdoor system.  

Depending on equipment and type of controls used, transformers 

may need to be wired in phase to each other or in phase to ground. 

To properly wire two low‐voltage transformers in phase, the primary 

and secondary windings of both transformers must be connected so 

that current flow is in the same direcƟon in each transformer.  L1 

and L2 must be connected as shown in Figure 2‐20(a) on the 

transformer, L1 to L1 and L2 to L2. 

The secondary windings of both transformers must be connected in 

parallel and in phase.  To check the phasing connect one 24‐volt lead 

from each transformer together.  With a voltmeter, measure the 

voltage between the two other 24‐volt connecƟons.  If in phase, the 

voltmeter will indicate 0 volts; if out of phase, the voltmeter will 

indicate 48 volts.  If the measurement is 48 volts, the wires on either 

the primary or secondary side of the transformer must be reversed. 

Fig. 2‐19(b):  230/120 V  

three‐phase with high‐leg 

Fig. 2‐19(c):  230/120 V three‐

phase 

Fig. 2‐19(a): Single‐phase 

230/120 V 

Fig. 2‐20(a):  Transformer phasing