Background Image
Table of Contents Table of Contents
Previous Page  77 / 156 Next Page
Information
Show Menu
Previous Page 77 / 156 Next Page
Page Background

Electrical Theory & Applications for HVACR  

Chapter 3:  Motors 

Page 65 

CURRENT RELAY

The current relay is used on motors normally rated one horse power or less

(See fig. 3‐15) .   The coil of a current relay is made of 18‐ to 14‐gauge copper 

wire for low resistance (usually less than one ohm).  The main terminals of a 

current relay are L, M, and S, with L connecƟng to line, M connecƟng to run 

winding, and S connecƟng to the start winding or start capacitor.  Since the 

coil is connected in series with the run winding, it must have a very low 

voltage drop and be able to carry the amperage draw of the motor.  The 

contacts are normally open (NO) and the sequence of operaƟon is: 

Motor off

—contacts open 

Motor energized

—contacts closed 

Motor starƟng amperage drops

—contacts open   

StarƟng current (LRA) through the coil creates a magneƟc field that pulls the solenoid up to close the 

contacts in series with the start winding or start capacitor.  As the motor comes up to speed, 

amperage decreases, magneƟc force reduces, and gravity pulls the solenoid down to open the start 

contacts. 

To check the contacts, an ohmmeter can be connected to the L and S terminals.  There should be 

conƟnuity with the relay turned upside down.  Due to movement and the way contacts close, the 

relay should be turned over three or four Ɵmes and checked each Ɵme.  Usually, a coil failure is easily 

detected by a visual inspecƟon for a burnt spot and a check for conƟnuity between L and M. 

POTENTIAL RELAY

A potenƟal or voltage relay has a coil and set of normally closed contacts wired in series.  The main 

terminals of a potenƟal relay are 1, 2, and 5.  Terminal 1 connects to the start capacitor, terminal 2 to 

the start winding at the run capacitor, and terminal 5 to the common of the compressor (See fig. 3‐

17).   Note: The leg of line voltage feeding a run winding must also feed the capacitors. 

A relay coil is idenƟfied as terminals 2 and 5 and has a very high resistance.  The normally closed (NC) 

contact is idenƟfied as terminals 2 and 1.  The relay coil is wired parallel to the start winding.  

Contacts are wired in series with the start capacitor and the line feeding the run winding.  The relay 

coil is energized by the counter (back) electromoƟve force from the start winding.  Voltage induced in 

the start winding is greater than applied line voltage.  Because the start winding has a higher 

resistance and more turns than the run winding, it acts like a step‐up transformer.  As the rotor 

begins to turn, magneƟc lines of flux cut through the windings at a faster rate, causing the back EMF 

to increase with the rotor speed.  As the compressor gets to 75 percent operaƟng speed, voltage 

becomes high enough to energize the potenƟal relay coil and the contact opens.  The relay has three 

raƟngs: conƟnuous coil voltage, contact pick‐up voltage (open), and contact drop‐out voltage (close). 

Fig. 3‐24:  Current relay 

Fig 3‐25:  PotenƟal relay wiring 

Fig. 3‐26:  PotenƟal relay 

Coil