Background Image
Table of Contents Table of Contents
Previous Page  78 / 156 Next Page
Information
Show Menu
Previous Page 78 / 156 Next Page
Page Background

Page 66 

Chapter 3:  Motors 

Electrical Theory & Applications for HVACR  

SOLID STATE AND PTC

There are two solid‐state or electronic starƟng devices: posiƟve 

temperature co‐efficient thermistors (PTCs) and electronic 

relays.  Either of these can be wired in series with a start 

winding, with or without a start capacitor (See fig. 3‐14). 

A PTC has a resistance of approximately 5 to 15 ohms cold.  As 

current passes through, the PTC heats up and resistance 

increases to 10,000 ohms or higher.  This high resistance 

virtually stops current flow to the start winding and/or 

capacitor.  A PTC can be checked by wiring it in series with a 100 

waƩ, 120 Vac incandescent light bulb.  When power is applied, 

the light should be bright, and then fade out in about 60 seconds. 

An electronic start relay relies on either voltage sensing or Ɵme delay to disconnect the starƟng 

circuit.  It is wired with only two leads in series with the start capacitor, connected to the run and 

start terminals of the motor. 

CALCULATING MOTOR HORSEPOWER

Motors are rated according to the amount of torque they can produce.  This turning power is 

measured in horsepower.  The electrical consumpƟon is measured in waƩs.  A one horsepower motor 

consumes approximately 746 waƩs.  Thus, a five horsepower motor will use approximately 3,730 

waƩs (5 X 746=3730).  This formula assumes 100 percent efficiency.  When waƩage and voltage are 

known, Ohm’s Law allows us to determine amperage draw at full load condiƟons.  True horsepower 

must take into account the power factor, which is approximately 0.95, motor slippage and fricƟon.  

Field calculated waƩage will be higher as much as 30% or more depending on type of motor. 

SERVICE FACTOR

Service factor (SF) is a mulƟplier marked on data plates that indicates the total permissible 

horsepower loading when the motor is operaƟng at rated voltage and frequency.   

Example: 

A motor rated at 0.75 Hp with a service factor of 1.2 is rated at  0.9 Hp.  

(0.75 HP X 1.2 SF = 0.9Hp) 

TIP:  

When replacing a motor, the replacement motor’s horsepower mulƟplied by its service factor 

must be equal to or greater than the original motor’s horsepower mulƟplied by service factor. 

LOCKED ROTOR AMPS (LRA)

At start‐up, before a rotor starts to rotate or if it is locked, current flow in the motor is determined by 

the resistance of the windings.  StarƟng current (inrush current) is about six Ɵmes higher than normal 

running amperage.  This high current flow is called locked rotor amps (LRA).  As the motor picks up 

speed, counter‐EMF is generated and reduces current flow.  At operaƟonal speed, current flow is 

determined by resistance of the run winding, counter‐EMF generated by the motor, and the load 

placed on the motor. 

Fig. 3‐27:  PTC relay with capacitor