Background Image
Table of Contents Table of Contents
Previous Page  73 / 156 Next Page
Information
Show Menu
Previous Page 73 / 156 Next Page
Page Background

Electrical Theory & Applications for HVACR  

Chapter 3:  Motors 

Page 61 

A start capacitor can be removed from a start winding circuit by a centrifugal switch, current relay, 

PTC, potenƟal relay (voltage relay), or  an electronic Ɵming device.  

IDENTIFYING HERMETIC MOTOR TERMINALS

Technicians will oŌen have to idenƟfy run (R), start (S), and common (C) terminals or check hermeƟc 

motor windings for an open, a short, or a grounded condiƟon. 

Note: When checking hermeƟc compressors, remember that terminals are under high pressure and 

could blow out of the shell, causing serious injury or death. 

If any of the following condiƟons is found, the motor must be replaced: 



Any set of terminals measure 0 ohms (the winding is shorted)  



Any set of terminals measure infinity (the winding is open) 



Each terminal must be checked to ground.  If a measureable resistance is detected, the motor is 

grounded. 



If the internal overload is open, there will be measureable resistance between start and run 

terminals and infinity between common to start or run. The compressor should be allowed Ɵme 

to cool and rechecked.   

Fig. 3‐18(a) 

COMMON 

Fig. 3‐18(b) 

RUN 

Fig. 3‐18(c) 

START 

Fig. 3‐18(d) 

Step 1:  

Ohm each set of terminals with all wiring 

removed and record the informaƟon as shown in 

Figure 3‐18(a). 

Step 2:  

The terminals with the highest ohm 

measurement (between run and start) idenƟfy 

the other terminal as the common, shown in 

Figure 3‐18(b). 

Step 3:  

Place one test lead of the ohmmeter on 

the common terminal and the other on the 

terminal with the lowest measurement.  This is the 

run terminal.  See Figure 3‐18(c). 

Step 4:  

The remaining terminal with the 

middle resistance measurement is the start 

terminal, shown in Fig. 3‐18(d).